Skip to Content
Contact
mail
call

THE DIFFERENCE BETWEEN INDOOR VENTILATION AND INDOOR AIR PURIFICATION

More outside air, higher heating costs – and still smoke in the hall. Or clean air that becomes stuffy in the afternoon. Both happen when hall ventilation and hall air cleaning are confused. This article shows what the two systems achieve, how they differ, and how to combine them correctly.

Hall ventilation: exchanging air

A mechanical hall ventilation blows in treated outside air and sucks out hall air. Depending on the concept, it mixes the air throughout the room (mixed ventilation) or brings the supply air close to the floor, allowing warm, contaminated air to rise and be removed above (stratified ventilation).

Its strength: It provides the required fresh air and removes heat loads from machines and processes. Its limit: Particles and smoke are only diluted and carried outside. Every cubic meter of outside air must be heated in winter and possibly cooled in summer. Without heat recovery, a lot of energy is lost through the exhaust.

Hall air cleaning: cleaning air

Hall air cleaning addresses where the extraction at the source does not capture everything: when handling workpieces, opening machine enclosures, or at workstations without a fixed extraction point. The system sucks in the contaminated hall air, separates fine dust, welding smoke, or oil and emulsion mist in the filter, and returns the cleaned air to the hall.

Your strength: The heat remains in the hall, and diffuse emissions are separated instead of diluted. Your limitation: It does not replace fresh air. It does not remove CO₂, humidity, and heat loads. For carcinogenic substances, strict regulations apply to air recirculation, such as TRGS 560 in Germany.

The comparison at a glance

Criterion

Hall ventilation

Hall air purification

Principle

Hall air is exchanged for outside air

Hall air is filtered and recirculated (recirculation)

Effect on particles and smoke

Dilutes the load and carries it outside

Separates particles, smoke and aerosols in the filter

Fresh air, CO₂, humidity

Yes, core task

No, no substitute for outside air

Heat loads

Removes heat with the exhaust air

Heat remains in the hall

Energy in winter

Supply air must be heated; heat recovery reduces losses

Heat remains in the hall, the outside air proportion can be reduced to the necessary level

Typical use

Basic supply, heat removal, gaseous loads

Diffuse emissions, e.g. sweat smoke, oil and emulsion mist, fine dust

What do you really need?

In practice, there is a clear order:

1.    Capture at the source: Suction emissions as close as possible to the point of origin. This is the most effective and often the cheapest measure.

2.    Hall air cleaning: separating the remainder of diffuse emissions that are not captured at the source.

3.    Hall ventilation: supplying the necessary fresh air and removing heat loads with heat recovery.

Most production halls therefore do not need one or the other, but a coordinated overall concept. The cleaner the hall air is through capture and filtration, the more the proportion of outside air can be limited to the necessary level.

Interesting facts

FAQ


No. It removes particles and aerosols, but does not supply fresh air or remove CO₂, moisture, or heat. A minimum amount of outside air is always necessary.

No. It complements it. What is captured at the source does not need to be distributed in the hall air and recaptured.

It can, especially during the heating period: The cleaned, warm air stays in the hall, and the proportion of outside air can be reduced to the necessary level. How much it saves depends on the process, hall size, and operating hours.

Kappa analyzes emission sources, air volumes, and the hall situation on-site and plans capture, hall air cleaning, and ventilation as a system.